Clima Sensor US
5 In Stock
Attention: Due to the current delivery situation, please request the product by email or via our contact form!
This sensor has a GPS receiver. It is used to determine position and time, and the position of the sun is also calculated from this. Position, time and position of the sun are output serially.
The compact design, simple installation and the various data output options are the basis for use in many areas:
- building management system
- traffic control technology
- meteorology
- energy supply
- environmental monitoring
Variant NHTFB = precipitation, brightness, temperature, humidity, air pressure
Variant TFB = temperature, humidity, air pressure
Variant NH = Precipitation, Brightness
Variant Wind = wind speed, wind direction
Technical data:
temperature | |
measuring range | -40 ... +80 °C |
accuracy | ±0.3 K ( @ 25 °C ) |
relative humidity | |
measuring range | 0 ... 100 % rel. F. |
accuracy | ± 1.8% relative F. (10% ... 90% relative F.) |
air pressure | |
measuring range | 300 ... 1100 hPa |
accuracy | ±0.25 hPa (+10 °C ... +35 °C) |
brightness | |
measuring range | 0 ... 150 kLux |
accuracy | 3% of the relative measured value |
precipitation | |
measuring range | 0.001 ... 10 mm/min |
wind speed | |
measuring range | 0 ... 60 m/s |
resolution | 0.1 m/s (standard) |
accuracy | ±0.3 m/s rms ( < 5 m/s ) / ±3 % rms ( 5 m/s ... 60 m/s ) |
wind direction | |
measuring range | 0 ... 360 ° |
resolution | 1 ° / 0.1 ° in special telegrams |
accuracy | ±2 ° WG > 2 m/s |
virtual temperature | |
measuring range | -40 ... +80 °C |
resolution | 0.1 K |
accuracy | ±0.5 K |
digital data output | |
interface | RS485 / RS422 |
baud rate | 1200 ... 921600 baud |
data values | Various measurement data, date, time, checksum, etc. |
output rate | 1 per 10 msec up to 1 per 60sec |
status signals | Heating, measuring section failure, section temperature |
protocol | ASCII or MODBUS RTU (default) |
analog data output | |
type | max. 8 x 0 ... 10 V |
wind speed | 0 ... 10 V |
Current output | max. 400 Ω |
Wind direction | 0 ... 10 |
voltage output | min. 2000 Ω |
output parameters | Wind speed, wind direction, brightness, precipitation, rel, humidity, air temperature, air pressure, etc. |
operating voltage | |
electronics | 6 .. 60V DC or 10 .. 42 V AC / 1.2 W |
Heating | 24 V AC/DC, typ 25W |
Generally | |
bus service | up to 98 sensors |
Electrical connection | 19-pin connector (connection cable must be ordered separately) |
assembly | on mast tube 1.5`` |
Housing | plastic LEXAN (polycarbonate, UV-stabilized) |
protection class | IP 67 |
Dimensions | Ø 150 x 175 mm |
Weight | 0.9 kg |